EV Charger Circuit & Breaker Size Calculator

EV chargers are continuous loads, so the circuit must be sized at 125% of charger current. Enter your charger's amps to get the breaker, wire and power.

From an NEC 220.83 calculation, utility data or a load monitor. Unsure? Ask your electrician.

Charging power can't exceed this, whatever the wall unit's rating.

Breaker size

—

Copper THHN (conduit)

—

Copper NM-B (Romex)

—

Charger max power

—

Car actually uses

—

Your inputs are saved in the link.

Embed the EV Charger Circuit & Breaker Size Calculator

Free to use on your blog or dealership site. Paste this HTML where you want the calculator to appear.

Free, no-obligation

Get Home Charger Installation Quotes

Compare licensed, EV-certified electricians near you. Permits, load calculation and inspection handled.

Get quotes →

How EV charger circuits are sized

The US National Electrical Code treats EV charging as a continuous load (NEC 625.41 and 210.19/210.20): the branch circuit and breaker must be rated for at least 125% of the charger's maximum current. The conductor must then be rated for at least the breaker size, using the correct temperature column of NEC Table 310.16.

ChargerBreakerCopper THHN (75°C)Copper NM-B (60°C)Power @ 240 V
16 A20 A12 AWG12 AWG3.8 kW
24 A30 A10 AWG10 AWG5.8 kW
32 A40 A8 AWG8 AWG7.7 kW
40 A50 A8 AWG6 AWG9.6 kW
48 A60 A6 AWG4 AWG11.5 kW
80 A100 A3 AWG1 AWG19.2 kW

Important: this calculator is for planning only. Local amendments, conductor terminal ratings, voltage drop on long runs, conduit fill and ambient temperature can all change the requirement. EV charger installation requires a permit in most jurisdictions — always use a licensed electrician.

Not sure how many amps you need? Read 32A vs 40A vs 48A: which one does your car actually use?

Formulas, assumptions and data sources are documented on our methodology page. Results are estimates; your utility bill and vehicle may differ.

Frequently asked questions

What size breaker do I need for a 48 amp EV charger?

EV charging is a continuous load, so the NEC requires the circuit to be rated at 125% of the charger current: 48 A × 1.25 = 60 A. A 48 A charger needs a 60 A breaker and must be hardwired; a NEMA 14-50 receptacle cannot be used above 40 A.

What wire size is needed for a 60 amp EV charger circuit?

With copper THHN/THWN in conduit (75°C column), 6 AWG is rated 65 A, so it works on a 60 A breaker. With NM-B (Romex) cable you must use the 60°C column, where 6 AWG is only 55 A, so 4 AWG copper is needed. Always confirm terminal ratings and local code with your electrician.

Can I use a 50 amp breaker with a 40 amp charger?

Yes — 40 A × 1.25 = 50 A, which is the standard pairing. It is also the most common setup for a plug-in charger on a NEMA 14-50 outlet.

Do I need a panel upgrade for an EV charger?

Not always. An NEC 220.83 load calculation or a load-management (energy management) device can often fit a charger on an existing 100–200 A service. If your panel is near capacity, a lower-amperage charger or smart load sharing is usually far cheaper than a service upgrade.